Answer:
Ferroamp's DC distributions contain 5, 8, or 15 DC fuse pairs for component connection. When purchasing a DC distribution, 15 A DC fuses are installed in the fuse holders. This means that it is possible to connect batteries with a maximum charging and discharging power of under 11.4 kW.
By replacing the fuses with 20 A DC fuses, it becomes possible to connect batteries with a maximum charging and discharging power of under 15.2 kW. The largest size of fuses that can be used in the fuse holders is 32 A, enabling the installation of batteries with a maximum charging and discharging power of under 24.3 kW.
It is important to note that there is a circuit breaker with a rated current of 63 A on each row of the DC distribution. Therefore, it is not possible to install more per row than the equivalent of a maximum current of 63 A.
Fuse size | Maximum charging and disscharging power for battery |
15 A | 11,4 kW |
20 A | 15,2 kW |
32 A | 24,2 kW |
For batteries with a power exceeding 24 kW, a separate DC distribution cabinet needs to be built. You can read more about it here.
We constantly want to improve the content in the Knowledge Database and would appreciate it if you give feedback on our articles. Does all the information exist, is there anything that needs to be clarified or is there any information that is missing that would help installing or using the EnergyHub system in general? You can give us feedback by choosing if the article was helpful or not in the options below.
If you need to get in contact with Ferroamp's Technical Support or if you have any questions about the system, you can do so by creating a ticket here.
Was this article helpful?
That’s Great!
Thank you for your feedback
Sorry! We couldn't be helpful
Thank you for your feedback
Feedback sent
We appreciate your effort and will try to fix the article