Is there a requirement for a separate DC breaker in Ferroamp's DC network?

*NOTE: The information below is directed towards installers. Only trained electricians are allowed to install Ferroamp’s products.  


Answer:


There is no requirement for a separate DC breaker in the EnergyHub system. However, a DC breaker can be advantageous for tasks such as disconnecting the DC network during service and maintenance work. It can be placed on the outgoing DC cable from the EnergyHub between the EnergyHub and the rest of the DC network. In Ferroamp's DC distribution, there are DC breakers that are approved load disconnectors. If the DC distribution is easily accessible near the EnergyHub, these can be used as DC breakers in the system. However, if the DC distributions are mounted near the SSOs, for example, on a wall near the ceiling, a separate DC breaker near the EnergyHub can facilitate the disconnection of the DC network.

The DC breaker should be rated for 1000 V DC and the maximum theoretical currents it needs to interrupt. This is calculated based on the maximum power that can be transmitted through the cable, considering the maximum power that can be delivered by the SSOs and battery.


We constantly want to improve the content in the Knowledge Database and would appreciate it if you give feedback on our articles. Does all the information exist, is there anything that needs to be clarified or is there any information that is missing that would help installing or using the Ferroamp system in general? You can give us feedback by choosing if the article was helpful or not in the options below. 


If you need to get in contact with Ferroamp's Technical Support or if you have any questions about the system, you can do so by creating a ticket here